Extra Losses in Imperfect Closed Grids

Authors

  • Josifs Survilo Riga Technical University
  • Edite Biela Riga Technical University

DOI:

https://doi.org/10.2478/v10144-011-0003-0

Keywords:

electricity quality, equalizing current, non-uniform grids, power losses, two-terminal line

Abstract

Closed grids consist of two-terminal power lines or/and of rings (loops). In non-uniform two-terminal lines, equalizing and circulating currents appear, in rings - circulating current. These currents cause extra power losses. Those losses are equal to the product of summary resistance and squared said extra currents and are independent of the direction of said currents. Equalizing current causes considerable losses by phase discrepancy of terminal voltages even when voltage magnitudes are equal. Equalizing current losses do not exceed 1/4 of load losses when terminal voltage difference is equal to maximum load voltage loss. The degree of non-uniformity of inhomogeneous rings can be estimated by inhomogeneous factor. The increased reliability and higher electricity quality in distribution grids can be attained by use of uniform or ameliorated ringed grids but the reservation can be implemented by controllable links between adjacent rings.

References

A. Vanags, Elektriskie tīkli un sistēmas, I daαa. Rīga, RTU izdevniecība, 2005, Iev. un 6.nodaαa.

Turan Gönnen, Electric Power Distribution System Engineering. London, New York, CRC Press Taylor & Francis Group, 2008, chapter 4; 5.

В. Блок, Электрические сети и системы, Москва, "Высшая школа", 1986, глава 4.

В. Идельчик, Электрические системы и сети, Москва, Энергоатомиздат, 1989, глава третья.

K. Tabaks, Elektrotehnikas teorētiskie pamati. Stacionāri procesi lineārās ķēdēs, Rīga, "Zvaigzne", 1985, 2. nodaαa.

J. Survilo, "A ringed non-uniform network: how to raise its efficiency", Latvian journal of physics and technical sciences. No 6. Riga, 2008, p.20-32.

J. Survilo, "Enhancement and comparison of simple types of closed networks", Latvian journal of physics and technical sciences. No 9. Riga, 2009, p.36-50.

Downloads

Published

2011-01-01

How to Cite

Survilo, J., & Biela, E. (2011). Extra Losses in Imperfect Closed Grids. Electrical, Control and Communication Engineering, 28(1), 19-24. https://doi.org/10.2478/v10144-011-0003-0